Electrical · power quality

Power Factor Calculator

Power triangle solver, capacitor correction, and UK reactive-charge estimator.
S² = P² + Q²
100 kW · PF 0.80

Power triangle

any two

Quick select

UK-focused

The triangle

Voltage vs. current

Correction

Capacitor sizing & UK reactive-charge estimate

Correct to a target PF

V
Hz

UK DNO reactive charge

Estimated monthly saving after correction
£0
Field notes

What power factor actually costs you

How it works

Real, reactive and apparent power

Only real power (kW) does useful work — turning motors, producing heat and light. Inductive equipment like motors and transformers also draws reactive power (kVAR), needed to build magnetic fields but returned to the supply every cycle rather than consumed. The supply still has to carry both, so the actual current flowing is set by the apparent power (kVA) — the hypotenuse of a right triangle with real and reactive power as its two legs. Power factor is simply PF = P/S = cos φ, and it's always somewhere between 0 (all reactive, no useful work) and 1 (perfectly efficient, no phase shift at all).

Worked example

A 100 kW load running at 0.80 PF draws 125 kVA from the supply and 75 kVAR of that never does any work. Correcting to 0.95 — the UK DNO reactive-charge threshold — needs 42.1 kVAR of capacitance, and drops the current draw by roughly 26% for the exact same 100 kW of real work.

Why do UK electricity bills penalise low power factor?

Every DNO in the UK builds its network around a design power factor of 0.95. A site running well below that forces more current down the same cables to deliver the same useful power, which is exactly why UK Power Networks' own connection terms require no less than 0.95 PF, and why most DNOs apply reactive-power charges below that threshold.

Why does correcting power factor need a capacitor, not a bigger cable?

A capacitor's reactive power is the mathematical opposite of an inductor's — it leads instead of lags. Placed in parallel with an inductive load, it supplies the load's reactive power locally instead of drawing it from the supply, which is what shrinks the current the cable actually has to carry.

How do I convert kVAR to microfarads?

Q = 2πfCV², rearranged to C = Q / (2πfV²) — where V is the voltage across each capacitor, not necessarily the supply voltage. Single phase uses the supply voltage directly. Three-phase delta divides the total by three (each capacitor carries a third of the kVAR at full line voltage). Three-phase star uses line/√3 per capacitor, which works out to three times the capacitance of delta.

Delta or star for a capacitor bank?

Delta, almost always. For the same correction it needs a third of the capacitance, because reactive power scales with the square of the voltage each capacitor sees. The trade is that every capacitor must be rated for full line voltage. Star banks appear where that voltage rating is the harder constraint, or where a neutral connection is wanted for unbalanced switching.

How much current does correction actually save?

At fixed real power, current scales with 1/PF — so going from 0.75 to 0.95 cuts it by 21%. Because losses go as I²R, the heating in cables and transformers falls by 38%, and the released kVA is headroom you can use for new load without upgrading the supply.

Can you over-correct power factor?

Yes — too much capacitance flips the phase the other way, giving a leading power factor, which some DNOs also penalise. Automatic capacitor banks switch stages on and off precisely to avoid overshooting past unity as the load changes through the day.

Does power factor affect a domestic electricity bill?

Not directly — UK domestic and small commercial supplies are billed on kWh alone. Reactive-power charges apply specifically to non-domestic sites with half-hourly metering, which is why this mostly matters for industrial and larger commercial premises.

Results are for reference only. Capacitor sizing here is a starting point, not a design: real correction has to account for harmonics, switching steps, and the site's load profile. Any installation must be specified and signed off by a qualified electrician.
Version history · 1 release
  1. v0.852026-07-28Power Factor: three-phase delta/star, capacitance in µF, real currents; correction panel now deep-linkable

Releases in which this page changed, newest last. Derived from the archived copy of every release, not from notes written afterwards — so it reflects what actually shipped. Site-wide passes are left out; they are in the full changelog.