Rule of thumb · ElectricalNº 207 / 238

Half a lead-acid battery is not yours to use

How long will my battery bank actually last?

Usable capacity is about 50% of a lead-acid nameplate and 80–90% of lithium — and the Peukert effect takes more again at high draw.

Why it works

Discharging lead-acid past half repeatedly destroys cycle life, so half the label is the working figure before anything else happens. Then the rating itself assumes a 20-hour discharge: pull 50 A from a 100 Ah battery and it delivers about 56 Ah, because the chemistry cannot keep up. Add an inverter taking 15% and the deductions multiply rather than add — a 1,200 Wh nameplate comes down to about 340 Wh of real work: 600 after depth of discharge, about 400 after a hard draw, 340 after the inverter.

When it fails

Lithium changes the arithmetic enough that the rule stops being useful: at a Peukert exponent near 1.05 the high-draw penalty nearly vanishes, and 90% depth of discharge is routine. And cold reverses the advantage — lead-acid loses a fifth of its capacity at 0 °C, while lithium holds capacity but must not be charged below freezing at all.

Do it exactly

Estimate with the rule, then check it against the calculator that models it properly.

Open Battery Sizing & Runtime →

More in Electrical

← PreviousThe ratio of dead time to time constant decides everything Next →Measure your own sweat rate; the guidelines fit almost nobody

Browse the full Rulebook →

Rules of thumb are approximations, offered to get you to the right order of magnitude fast. Check anything load-bearing against its source or the exact tool. Privacy · Terms

© 2026 Rules of Thumb · Runs entirely in your browser